load flow

In reference to the power system reactance diagram, all values are given in pu. Determine the followings:

 

  1. Construct the bus admittance matrix for the power system shown in Fig. 1
  2. Use Gauss-Seidel method to solve the load flow problem

 

Table 1: Impedances and line charging (in p.u.) for the system shown in Fig.1

Bus code p-q

Impedance 

Shunt admittance 

1-12

0.02+j0.16

j0.03

1-4

0.015+j0.12

j0.024

1-3

0.015+j0.13

j0.024

1-2

0.03+j0.25

j0.031

12-11

0.025+j0.20

j0.021

12-5

0.016+j0.09

j0.015

12-4

0.016+j0.10

j0.015

2-8

0.06+j0.60

j0.04

3-8

0.03+j0.28

j0.04

3-4

0.018+j0.16

j0.03

4-5

0.014+j0.1

j0.03

4-9

0.008+j0.065

j0.012

9-8

0.045+j0.40

j0.038

9-7

0.02+j0.18

j0.025

9-6

0.04+j0.38

j0.036

9-10

0.035+j0.32

j0.034

8-7

0.045+j0.40

j0.042

7-6

0.045+j0.40

j0.042

6-10

0.015+j0.13

j0.020

 

 

 

 

Table 2: Bus data for the system shown in Fig. 1

Bus code

Vinitial

Pg

Qg

Pl

Ql

1(slack)

1.0+j0

0

0

0

0

2

1.0+j0

0

0

0.66

0.26

3

1.0+j0

0

0

0.50

0.15

4

1.0+j0

0

0

0.54

0.16

5

1.0+j0

0

0

0.42

0.18

6

1.0+j0

0

0

0.64

0.28

7

1.0+j0

0.

0

0.60

0.26

8

1.0+j0

0.68

 

0.18

0.06

9

1.02+j0

0.84

 

0.24

0.09

10

1.01+j0

0.97

 

0.20

0.05

11

1.01+j0

0.85

 

0

0

12

1.03+j0

0.72

 

0.12

0.03

 

 

 
Looking for solution of this Assignment?

WHY CHOOSE US?

We deliver quality original papers

Our experts write quality original papers using academic databases.  

Free revisions

We offer our clients multiple free revisions just to ensure you get what you want.

Discounted prices

All our prices are discounted which makes it affordable to you. Use code FIRST15 to get your discount

100% originality

We deliver papers that are written from scratch to deliver 100% originality. Our papers are free from plagiarism and NO similarity

On-time delivery

We will deliver your paper on time even on short notice or  short deadline, overnight essay or even an urgent essay